EATON BiWire Flexi Installation Manual (PR215-216-520-03 15-03-16, PINSTFLEXIINST) March 2016 www.eaton.com 19
Installation Instructions
NO OTHER DEVICES ARE TO BE CONNECTED TO A ZONE
CONFIGURED FOR INTERLINKING.
THE UNLATCHING SETTING IS NOT TO BE USED WITH
DETECTION ZONES AS THIS WILL MAKE THE PANEL
NON-COMPLIANT.
Connecting the Input/Output Cables
Connect the cables (clearly labelled with the external
equipment reference) to the appropriate input or output
terminals, observing the correct polarity where applicable.
Figure 25: Interlink Settings
Figure 24: Interlink Wiring Diagram
CAUTION
NOTE
WARNING
Figure 23: Repeater Out Setting
MAKE SURE TO FOLLOW THE INSTALLATION GUIDES OF
ANY EXTERNAL EQUIPMENT AND CHECK THE CORRECT
WIRING POLARITY AND THAT THE EQUIPMENT IS
COMPATIBLE WITH THE BIWIRE FLEXI PANEL BEFORE
POWERING UP THE SYSTEM.
Connecting a Repeater Panel
Connect the cables from the repeater panel to the Repeater
terminals on the main board of the fire alarm panel, observing
the correct polarity (see Figure 22).
To enable the repeater output switch 2 of SW12 on the
panel main board must be changed to the “Repeater Output
On” setting (see Figure 23).
Interlinking Two Panels
Wire the two panels together as shown in Figure 26.
The EOLM-3 must be fitted for the zone circuits on both
panels to be monitored for fault conditions.
The 680ohm resistor must be fitted so that the zone input
will detect the fire condition and activate its fire alarm
devices.
In order for the Interlink to operate correctly the zone inputs
on both panels being used for interlinking must be set to
unlatched, therefore the associated switch on SW4 must be
set to the “Unlatched Zone x” setting (see Figure 25).
BiWire Flexi PanelBiWire Flexi Panel
www.acornfiresecurity.com
www.acornfiresecurity.com