EATON BiWire Flexi Installation Manual (PR215-216-520-03 15-03-16, PINSTFLEXIINST) March 2016 www.eaton.com 20
Installation Instructions
3.4 Option Board
Connecting the FRE and FPE Outputs
Connect the cabling from the fire alarm routing equipment
and fire protection equipment to the relevant terminals on
the option board.
As these outputs are monitored for short circuit and open
circuit faults conditions, the 6K8 resistor supplied should
be installed at the external equipment and not at the option
board terminals.
IF EITHER THE FRE OR FPE IS NOT BEING USED
THEN THE 6K8 RESISTOR SHOULD BE FITTED AT THE
APPROPRIATE TERMINAL ON THE OPTION BOARD. THIS
PREVENTS ERRONEOUS FAULTS CONDITIONS BEING
DISPLAYED ON THE PANEL.
Connecting the Zonal Outputs
Connect the cabling from the external equipment to the
relevant zone terminals on the option board.
These outputs are not monitored so there is no need for a
6K8 termination resistor.
Change the jumpers on the zonal relays to get them to
operate in either normally open or normally closed during
a fire alarm condition.
NOTE
Figure 26: Option Board Wiring Diagram
www.acornfiresecurity.com
www.acornfiresecurity.com