EATON BiWire Flexi Installation Manual (PR215-216-520-03 15-03-16, PINSTFLEXIINST) March 2016 www.eaton.com 21
Installation Instructions
3.5 Panel Configuration
Silence Mode Disabled
With switch 3 of SW12 on the panel main board set to
“Silence Mode Disabled” the panel will re-sound all fire
alarm devices after the panel has been silenced with any
new fire conditions detected.
Silence Mode Enabled
With switch 3 of SW12 on the panel main board set to
“Silence Mode Enabled” the panel will NOT re-sound the
fire alarm devices after the panel has been silenced
regardless of any new fire conditions detected.
3.6 Zone Configuration
Figure 27: Silence Mode Setting
Zone # BiWire Mode Standard Conventional IS Conventional
1 SW3.1 = N/A SW3.1 = OFF SW3.1 = ON
SW5.1 = ON SW5.1 = OFF SW5.1 = OFF
2 SW3.2 = N/A SW3.2 = OFF SW3.2 = ON
SW5.2 = ON SW5.2 = OFF SW5.2 = OFF
3 SW3.3 = N/A SW3.3 = OFF SW3.3 = ON
SW5.3 = ON SW5.3 = OFF SW5.3 = OFF
4 SW3.4 = N/A SW3.4 = OFF SW3.4 = ON
SW5.4 = ON SW5.4 = OFF SW5.4 = OFF
5 SW3.5 = N/A SW3.5 = OFF SW3.5 = ON
SW5.5 = ON SW5.5 = OFF SW5.5 = OFF
6 SW3.6 = N/A SW3.6 = OFF SW3.6 = ON
SW5.6 = ON SW5.6 = OFF SW5.6 = OFF
7 SW3.7 = N/A SW3.7 = OFF SW3.7 = ON
SW5.7 = ON SW5.7 = OFF SW5.7 = OFF
8 SW3.8 = N/A SW3.8 = OFF SW3.8 = ON
SW5.8 = ON SW5.8 = OFF SW5.8 = OFF
Figure 28: Zone Mode Setting
SW5 Zone Mode SW3 Intrinisic Mode
www.acornfiresecurity.com
www.acornfiresecurity.com