3.7 Detector Fitting
All detector heads should now be fitted to the bases
(following the device installation guide), prior to the
installation being tested.
The BiWire detectors can be configured for either latched or
non-latching fire condition.
When the detectors are configured for latched mode then
care must be taken that before any zone is re-enabled that
a walk round of the zone is carried out to check that all
detectors and manual call points are not latched in the fire
condition.
If there are no detectors or manual call points showing the
fire condition then the zone can be re-enabled at the panel.
FAILURE TO FOLLOW THE INSTRUCTIONS ABOVE
WILL RESULT IN THE PANEL ENTERING A FULL ALARM
CONDITION WHICH WILL EVACUATE THE SITE AND
ACTIVATE ANY OTHER EQUIPMENT ATTACHED TO THE
FIRE ALARM SYSTEM.