EATON BiWire Flexi Installation Manual (PR215-216-520-03 15-03-16, PINSTFLEXIINST) March 2016 www.eaton.com 29
Operating Instructions
6.7 Individual Zone Test
This function is only available at access level 2.
This function will allow individual zones to be placed in the
zone test mode.
Enter the access code 3112
Press “Test” button (2).
The zone currently in test mode will have its associated
disabled indicator lit and all zones not in test mode will
have their associated disabled indicators unlit.
The function always starts at Zone 1.
When an item is selected for test mode its disable
indicator will change from unlit to lit.
When an item is selected for normal operation its disable
indicator will change from lit to unlit.
Press the following button sequences for the required test
mode/normal operation:
Pressing “Select” button (3) will accept the selected test
zone and exit back to Access Level 1. The Test indicator
will remain lit and the zone disabled indicator will also
remain lit.
When a fire detection device or manual call point is
activated in the zone under test it will sound all fire alarm
devices for 3 seconds and then will automatically silence.
Any fire condition detected in any other zone will place the
system into full alarm condition and the fire alarm devices
will activate continuously.
To end the individual test mode the above selection
instructions should be carried out and the zone disabled
indicator changed to the unlit state.
6.8 Lamp Test
This function is available at access level 2.
Enter the access code 3112.
Press “Indicator Test” button (3).
Each indicator on the front of the panel will turn on in turn
and then turn off in turn (excluding the Power On indicator).
This function will immediately exit back to Access Level 1.
Item 2-Zone 4-Zone 8-Zone
Zone 1 3 3 3
Zone 2 2 + 3 2 + 3 2 + 3
Zone 3 2 (2 times) + 3 2 (2 times) + 3
Zone 4 2 (3 times) + 3 2 (3 times) + 3
Zone 5 2 (4 times) + 3
Zone 6 2 (5 times) + 3
Zone 7 2 (6 times) + 3
Zone 8 2 (7 times) + 3