EATON BiWire Flexi Installation Manual (PR215-216-520-03 15-03-16, PINSTFLEXIINST) March 2016 www.eaton.com 33
Technical Specifications
7.2 PSE Specification
BiWire Flexi Fire Panel
EFBW2ZONE-FLEXI EFBW4ZONE-FLEXI EFBW8ZONE-FLEXI
POWER SPECIFICATION
Mains Voltage 230V AC +10%/-15%, 50Hz
Mains Fuse 1 Amp Anti Surge
PSE RATINGS
Number of Batteries 2
Capacity 12V, 5Ah
Recommended Battery Yucell Y5-12 (Yuasa)
Battery Fuse 6.3A Anti Surge
Battery voltage (Charging Value) 27.3V DC @ 20°C
Recommended period for battery replacement 5yrs
PSE RATINGS
Output Voltage 18.75-30.7V
Maximum ripple voltage 425mVrms (1.2Vp-p)
Imin 39mA
Imax.A 2.1A
Imax.B 2.6A
Ri max 1Ω
PSE FAULT OPTIONS
MAINS OK (J4 pin4) >=3V Mains present, <=3V Mains fault
FAULT_CHARGER (J4 pin1) >=3V for 1s pulsed at 0.2Hz Charger OK
>=3V for 1s pulsed at 1Hz Charger fault
Steady high/low (no pulsing) PSE Micro fault
FAULT_BATTERY (J4 pin3) =0.17*(Vbat-0.6) Volts
0V (J4 pins2 and 10) reference
BiWire Flexi Fire Panel
EFBW2ZONE-FLEXI EFBW4ZONE-FLEXI EFBW8ZONE-FLEXI
POWER SPECIFICATION
Operating Voltage 18.75-30.7V
Nominal Current 1.7mA
7.3 EOLM-3 Specification
BiWire Flexi Fire Panel
EFBW2ZONE-FLEXI EFBW4ZONE-FLEXI EFBW8ZONE-FLEXI
POWER SPECIFICATION
Operating Voltage 18.75-30.7V
Nominal Current 1.4mA
7.4 EOLM-1 Specification