3. Access Levels
Regardless of the active access level the panel will continue
to monitor for fi re and fault conditions.
3.1 Access Level 1
This level of access is available to the general public and has
the following functions available:
Mute Buzzer
3.2 Access Level 2
This level of access is available to the Premises Management
only and is protected by an access code. The following
functions are available for this level:
Silence Fire Alarm Devices (BiWire Zones and
Conventional Sounder Circuits)
Sound Fire Alarm Devices (BiWire Zones and Conventional
Sounder Circuits)
Reset System
Mute Buzzer
Enable/Disable Zones, Sounders & FRE/FPE (when fi tted)
Individual Zone Test
Lamp Test
While the panel is at access level 2 the buzzer will give a fast
pulsing tone. If no function is selected within 30 seconds
the access level will time out and the panel will return to
access level 1.