Operating Instructions
9
6.5 Mute Buzzer
• This function is available at access level 1, 2 and 3.
• To silence the panel’s internal buzzer at access level 1 just
press the “Mute Buzzer” button.
• To silence the panel’s internal buzzer at access level 2 enter
the code 3112 and then press the “Mute Buzzer” button.
• This function will immediately exit back to Access Level 1.
6.6 Enable/Disable
• This function is only available at access level 2.
• Before using this function to re-enable a zone please refer
to 4.3 for more details.
• This function will allow the following to be disabled:
• Individual Zones
• All fi re alarm devices (On BiWire Zones and Conventional
Sounder Circuits)
• FRE (if fi tted)
• FPE (if fi tted)
• Enter the access code 3112.
• Press the “Disable/Enable” button (1).
• All previous disablements will have their associated
disabled indicator lit and all enablements will have their
associated disabled indicators unlit.
• The function always starts at Zone 1.
• When an item is selected for disablement its disable
indicator will change from unlit to lit.
• When an item is selected for enablement its disable
indicator will change from lit to unlit.
• Press the following button sequences for the required
enablement/disablement:
• Pressing “Select” button (3) will accept the selected
enablement/disablement and exit back to Access Level 1.
Item 2-Zone 4-Zone 8-Zone
Zone 1 3 3 3
Zone 2 1 + 3 1 + 3 1 + 3
Zone 3 1 (2 times) + 3 1 (2 times) + 3
Zone 4 1 (3 times) + 3 1 (3 times) + 3
Zone 5 1 (4 times) + 3
Zone 6 1 (5 times) + 3
Zone 7 1 (6 times) + 3
Zone 8 1 (7 times) + 3
Sounders 1 (2 times) + 3 1 (4 times) + 3 1 (8 times) + 3
FRE (if fi tted) 1 (3 times) + 3 1 (5 times) + 3 1 (9 times) + 3
FPE (if fi tted) 1 (4 times) + 3 1 (6 times) + 3 1 (10 times) + 3
March 2016 www.eaton.com
EATON BiWire Flexi User Manual (PR215-216-519-03 15-03-16, PINSTFLEXIUSER)