INSTALLATION AND OPERATION MANUAL 25-16732-A November 2019 www.eaton.com
Battery Connections
1. Connect the BLACK battery wire to the BLACK (-)
battery terminal of Battery B (Figure 23)
2. Connect the RED battery wire to the RED (+) battery
terminal of Battery A (shown as grey)
3. Connect the link cable between the two
remaining terminals
Connecting the Zone Cables
Connect the cables (clearly labelled with the zone numbers) to the
appropriate zone +/- terminals, observing the correct polarity. Figure 24
shows how different types of zone can be connected to a BiWire Flexi
Fire Panel.
If any of the zones are not used then the EOLM-3 must
remain fitted to the terminals of that zone to ensure the
system remains fault free.
CAUTION
DO NOT USE A HIGH VOLTAGE TESTER WHEN WIRING IS
CONNECTED TO ANY ELECTRONIC EQUIPMENT.
NOTE
IT IS IMPORTANT THAT ZONE CABLING IS CONNECTED
TO THE CORRECT ZONE INPUT OTHERWISE ANY FIRE OR
FAULT INDICATION ON THE PANEL WILL NOT MATCH THE
ZONE MAP OF THE SITE, AND WILL NOT BE COMPLIANT
WITH BS5839
Figure 23. Battery Connection
Figure 24. Panel Wiring Diagram