INSTALLATION AND OPERATION MANUAL 25-16732-A November 2019 www.eaton.com
Connecting the Input/Output Cables
Connect the cables (clearly labelled with the external
equipment reference) to the appropriate input or output
terminals, observing the correct polarity where applicable.
CAUTION
REFER TO THE INSTALLATION GUIDES OF ANY EXTERNAL
EQUIPMENT. CHECK THE CORRECT WIRING POLARITY
AND THAT THE EQUIPMENT IS COMPATIBLE WITH THE
BIWIRE FLEXI PANEL BEFORE POWERING
UP THE SYSTEM.
Interlinking Two Panels
Wire the two panels together as shown in Figure 25.
The EOLM-3 must be fitted for the zone circuits on both
panels to be monitored for fault conditions.
The 680ohm resistor must be fitted so that the zone input will
detect the fire condition and activate its fire alarm devices.
In order for the Interlink to operate correctly the zone inputs
on both panels being used for interlinking must be set to
unlatched, therefore the associated switch on SW4 must be
set to the Unlatched Zone x setting (see Figure 26).
WARNING
THE UNLATCHING SETTING IS NOT TO BE USED WITH
DETECTION ZONES AS THIS WILL MAKE THE PANEL
NON-COMPLIANT.
NOTE
NO OTHER DEVICES ARE TO BE CONNECTED TO A ZONE
CONFIGURED FOR INTERLINKING.
Connecting a Repeater Panel
Connect the cables from the repeater panel to the Repeater
terminals on the main board of the fire alarm panel, observing
the correct polarity (see Figure 24).
To enable the repeater output switch 2 of SW12 on the panel
main board must be changed to the Repeater Output On
setting (see Figure 27)
Figure 25. Interlink wiring diagram
Figure 26. Interlink settings
Figure 27. Repeater Output setting