19
INSTALLATION AND OPERATION MANUAL 25-16732-A November 2019 www.eaton.com
3.5 Panel Configuration
Silence Mode Disabled
With switch 3 of SW12 on the panel main board set to Silence
Mode Disabled the panel will re-sound all fire alarm devices
after the panel has been silenced with any new fire conditions
detected (Figure 29).
Silence Mode Enabled
With switch 3 of SW12 on the panel main board set to Silence
Mode Enabled the panel will NOT re-sound the fire alarm
devices after the panel has been silenced regardless of any
new fire conditions detected.
Zone Configuration
Set SW3 and SW5 as shown in Figure 30 and the
accompanying table.
Zone # BiWire Mode Standard Conventional Intrinsically Safe Conventional
1 SW3.1 = N/A SW3.1 = OFF SW3.1 = ON
SW5.1 = ON SW5.1 = OFF SW5.1 = OFF
2 SW3.2 = N/A SW3.2 = OFF SW3.2 = ON
SW5.2 = ON SW5.2 = OFF SW5.2 = OFF
3 SW3.3 = N/A SW3.3 = OFF SW3.3 = ON
SW5.3 = ON SW5.3 = OFF SW5.3 = OFF
4 SW3.4 = N/A SW3.4 = OFF SW3.4 = ON
SW5.4 = ON SW5.4 = OFF SW5.4 = OFF
5 SW3.5 = N/A SW3.5 = OFF SW3.5 = ON
SW5.5 = ON SW5.5 = OFF SW5.5 = OFF
6 SW3.6 = N/A SW3.6 = OFF SW3.6 = ON
SW5.6 = ON SW5.6 = OFF SW5.6 = OFF
7 SW3.7 = N/A SW3.7 = OFF SW3.7 = ON
SW5.7 = ON SW5.7 = OFF SW5.7 = OFF
8 SW3.8 = N/A SW3.8 = OFF SW3.8 = ON
SW5.8 = ON SW5.8 = OFF SW5.8 = OFF
Figure 29. Silence Mode setting
Figure 30. Zone Mode setting