22
INSTALLATION AND OPERATION MANUAL 25-16732-A November 2019 www.eaton.com
5. Maintenance
5.1 Daily Testing
To be conducted by the Premises Management.
• Check that the panel shows no fire or fault indications.
• If there are any fault conditions indicated then refer to the
“Status Indications” on page 8 to identify the fault.
5.2 Weekly Testing
To be conducted by the Premises Management.
•
Each week perform a Lamp Test to check that all visual and
audible indicators on the panel are functioning correctly
(refer to the “Lamp Test” on page 25).
•
Each week a different zone should be tested. Testing with
a manual call point is the simplest method as these can be
easily triggered with the key provided. Testing with a fire
detection device is more complex as it requires specialist
equipment and may not be possible for all premises. At a
minimum a different manual call point should be tested
each week.
•
Place the zone to be tested into test mode using the
Individual Zone Test (refer to page 25 for more details)
•
Record the weekly test results in the log book.
5.3 Quarterly Testing
To be conducted by the Competent Person.
•
Check all previous log book entries and verify that any
corrective actions had been taken.
•
Carry out the weekly test and record the results in the log
book.
•
Visually inspect the batteries and their connections.
•
Disconnect the mains supply and check that the fire system
is capable of supplying the fire alarm devices by operating a
call point.
5.4 Yearly Testing
To be conducted by the Competent Person.
•
Carry out the weekly test and record the results in the log
book.
•
Carry out the Quarterly testing.
•
Test ALL fire detection devices and manual call points.