INSTALLATION AND OPERATION MANUAL 25-16732-A November 2019 www.eaton.com
6. Operating Instructions
6.1 Multi-Function Buttons
The numerical value in the centre of the button is used to
enter access codes for level 2 and 3.
If the text in the centre of the button appears above a line (or
there is no line) then this function is applicable at access level
2. If the text in the centre of the button appears below a line
then this function is applicable at access level 3.
The text above button 3 indicates that this button is the Select
button during Disable/Enable and Individual Zone Test
functions.
6.2 Silence Fire Alarm Devices
This function is only available at access level 2 and when the
alarms are sounding.
Enter the access code 3112.
Press the Silence/Sound Alarms button.
Only the fire alarm devices will stop sounding, the panel
buzzer will continue sounding.
This function will immediately exit back to Access Level 1.
6.3 Sound Fire Alarm Devices
This function is only available at access level 2 and when the
alarms are silent.
Enter the access code 3112.
Press the Silence/Sound Alarms button.
Only the General Fire indicator will be lit, the panel buzzer
will sound a continuous tone and all fire alarm devices
will sound.
This function will immediately exit back to Access Level 1.
6.4 Reset System
This function is only available at access level 2.
Enter the access code 3112.
Press the Reset button.
This will stop all fire alarm devices sounding, will stop the
panel buzzer and will reset the panel.
The panel will return to the normal condition after
completing the indicator test routine which turns each
indicator on in turn and then turns them off in turn.
NOTE
WHEN PERFORMING A RESET, ANY TEST CASES WILL BE
CLEARED