INSTALLATION AND OPERATION MANUAL 25-16732-A November 2019 www.eaton.com
6.9 Self-test Mode
This function is only available at access level 3.
Enter the access code 2321.
Press the Test button .
The Test indicator will slow flash and the buzzer will give a
slow pulsing tone.
The fire indicator on every detector head will turn on.
This function is useful for checking that each head is fitted
correctly as the fire indicator will not turn on.
To end the self-test mode, enter the access code 2321 and
press button .
6.10 Walk Test Mode
This function is only available at access level 3.
Enter the access code 2321.
Press Indicator Test button .
The Test indicator will turn on and the buzzer will give a slow
pulsing tone.
This function places all zones in test mode and is used
during commissioning to test every fire detection device on
a zone.
Repeat the following for each zone (with fire detection
devices) in turn:
Activate the fire detection device or manual call point on
the zone.
All fire alarm devices will sound on all zones for 3
seconds and then will automatically silence.
The fire panel will then reset the zone from the
fire condition.
Repeat the above process until all fire detection device
and manual call points on the zone have been tested.
To end the walk test mode enter the access code 3112 or
2321 and press the Reset button.
If no fire detection device or manual call point is triggered
within 10 minutes of the walk test being started, the test
mode will timeout and return back to access
level 1/normal condition.