EasyManua.ls Logo

Eaton BiWire Flexi - PSE, EOLM-3, and EOLM-1 Module Specifications

Eaton BiWire Flexi
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
INSTALLATION AND OPERATION MANUAL 25-16732-A November 2019 www.eaton.com
EFBW2Zone-Flexi EFBW4Zone-Flexi EFBW8Zone-Flexi
Mechanical
Dimensions mm 375 (W) x 366 (H) x 134 (D)
Weight kg 2.25
Material PC ABS Front and Rear
Cabling
Cable Access 29 x 20mm drill positions - Slots for rear cable entry
Cable Type Firetuf FT120 / FP200
Cable type 2 core 1.5mm, 2 screened fire rated cable
500m (max per zone)
Compliance
Compliance to Standards EN54 Part 2 CIE and Part 4 PSE, BS5839, part1
7.2 PSE Specification
EFBW2Zone-Flexi EFBW4Zone-Flexi EFBW8Zone-Flexi
Power Specification
Mains Voltage 230V AC -10% / +15%, 50Hz
Mains Fuse 1 Amp Anti-Surge
Battery Details
Number of Batteries 2
Capacity 12V, 5Ah
Recommended Battery Yucell Y5-12 (Yuasa)
Battery Fuse 6.3A Anti-Surge
Battery voltage (Charging value) 27.3V DC @20%
Recommended period for battery replacement 5 years
PSE Ratings
Output voltage 18.75-30.7V DC
Maximum ripple voltage 425mV rms (1.2Vp-p)
Imin 39mA
Imax.A 2.1A
Imax.B 2.6A
Ri max 1Ω
PSE Fault Options
Mains OK (J4 pin 4) >=3V Mains present, <=3V Mains fault
Fault_Charger (J4 pin 1) >=3V for 1s pulsed at 0.2Hz Charger OK
>=3V for 1s pulsed at 1Hz Charger fault
Steady high/low (no pulsing) PSE Micro fault
Fault_Battery (J4 pin 3) =0.17* (Vbat-0.6) Volts
0V (J4 pins 2 and 10) reference
7.3 EOLM-3 Specification
EFBW2Zone-Flexi EFBW4Zone-Flexi EFBW8Zone-Flexi
Power Specification
Operating Voltage 18.75-30.7V DC
Nominal Current 1.7mA
7.4 EOLM-1 Specification
EFBW2Zone-Flexi EFBW4Zone-Flexi EFBW8Zone-Flexi
Power Specification
Operating Voltage 18.75-30.7V DC
Nominal Current 1.4mA