8. System Calculations
8.1 Zone Loading in Normal Condition
0.08
xxxxxxx
0.02 0.02 0.02 0.02 0.02 0.13
Detectors Call Points Sounder Bases Wall Sounders VADs Bases Wall VADs External I/O
Zone Total
= = = = = = =
=
Current per Device Type
(Max. 200mA)
Quantity
Device Current (mA)
mA
0.08
xxxxxxx
0.02 0.02 0.02 0.02 0.02 0.13
= = = = = = =
=
Current per Device Type
(Max. 200mA)
Quantity
Device Current (mA)
mA
0.08
xxxxxxx
0.02 0.02 0.02 0.02 0.02 0.13
= = = = = = =
=
Current per Device Type
(Max. 200mA)
Quantity
Device Current (mA)
mA
0.08
xxxxxxx
0.02 0.02 0.02 0.02 0.02 0.13
= = = = = = =
=
Current per Device Type
(Max. 200mA)
Quantity
Device Current (mA)
mA
0.08
xxxxxxx
0.02 0.02 0.02 0.02 0.02 0.13
= = = = = = =
=
Current per Device Type
(Max. 200mA)
Quantity
Device Current (mA)
mA
0.08
xxxxxxx
0.02 0.02 0.02 0.02 0.02 0.13
= = = = = = =
=
Current per Device Type
(Max. 200mA)
Quantity
Device Current (mA)
mA
0.08
xxxxxxx
0.02 0.02 0.02 0.02 0.02 0.13
= = = = = = =
=
Current per Device Type
(Max. 200mA)
Quantity
Device Current (mA)
mA
0.08
xxxxxxx
0.02 0.02 0.02 0.02 0.02 0.13
= = = = = = =
=
Current per Device Type
(Max. 200mA)
Quantity
Device Current (mA)
mA
7.5 Option Board Specification
EFBW2Zone-Flexi EFBW4Zone-Flexi EFBW8Zone-Flexi
Operating Voltage 18.75-30.7V DC
FRE Output Rating 24V, 50mA
Fuse 50mA PTC
EOLR 6.8KΩ
FPE Output Rating 24V, 50mA
Fuse 50mA PTC
EOLR 6.8KΩ
Number of Auxiliary Relays 2 4 8
Auxiliary Relays (Un-monitored) Type Volt-Free, Single Pole Double Throw
Rating 30V DC, 50mA
Fuse 500mA PTC
7.6 Cable Specification
Recommended Cable size 1-1.5mm2, Cable type - Firetuf FT120 /FP200
Manufacturer Draka UK to Standard - suitable for all applications described in BS5839-1:2013, 6, 8 & 9 and BS5266-1