8.2 Zone Loading in Alarm Condition
8.3 Battery Standby Time
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
Detectors Call Points Sounder Bases Wall Sounders VADs Bases Wall VADs External I/O Zone Total
= = = = = = =
=
Current per Device Type
Zone 1
(Max. 200mA)
Quantity
Device Current (mA)
mA
Zone 1
+
Zone 2
+
Zone 3
+
Zone 4
+
Zone 5
+
Zone 6
+
Zone 7
+
Zone 8
=
Total Zone Quiescent Current (ZQ)
mA
Zone 1
+
Zone 2
+
Zone 3
+
Zone 4
+
Zone 5
+
Zone 6
+
Zone 7
+
Zone 8
=
Total Zone Alarm Current (ZA)
mA
(4000 - (0.5 * (60 + ZA) ) ) / (51 + ZQ)
=
Standby Time Calculation
Hours
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 2
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 3
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 4
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 5
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 6
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 7
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 8
(Max. 200mA)
Quantity
Device Current (mA)
mA
VADs Base and Wall VADs
Sounder Only (High Volume) = 4.7mA
Sounder Only (Low Volume) = 2.6 mA
Beacon Only = 6.3mA
Combine the values relevant
to the site requirements to
get a more accurate power
consumption gure.
*
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
Detectors Call Points Sounder Bases Wall Sounders VADs Bases Wall VADs External I/O Zone Total
= = = = = = =
=
Current per Device Type
Zone 1
(Max. 200mA)
Quantity
Device Current (mA)
mA
Zone 1
+
Zone 2
+
Zone 3
+
Zone 4
+
Zone 5
+
Zone 6
+
Zone 7
+
Zone 8
=
Total Zone Quiescent Current (ZQ)
mA
Zone 1
+
Zone 2
+
Zone 3
+
Zone 4
+
Zone 5
+
Zone 6
+
Zone 7
+
Zone 8
=
Total Zone Alarm Current (ZA)
mA
(4000 - (0.5 * (60 + ZA) ) ) / (51 + ZQ)
=
Standby Time Calculation
Hours
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 2
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 3
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 4
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 5
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 6
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 7
(Max. 200mA)
Quantity
Device Current (mA)
mA
1.3
xxxxxxx
1.3 5.5 5.5 0.13
**
= = = = = = =
=
Current per Device Type
Zone 8
(Max. 200mA)
Quantity
Device Current (mA)
mA
VADs Base and Wall VADs
Sounder Only (High Volume) = 4.7mA
Sounder Only (Low Volume) = 2.6 mA
Beacon Only = 6.3mA
Combine the values relevant
to the site requirements to
get a more accurate power
consumption gure.
*