Eaton BladeUPS DoS Installation Instructions P-164000613—Rev 3 13
Section 8 Wiring and Cabling
CAUTION
Only qualified service personnel (such as a licensed electrician) shall perform the electrical installation.
Risk of electrical shock. Always verify utility power is switched off to the distribution point.
Note: Ferrite cores for wires are provided to meet EMI requirements. The input wires should pass through
the core from the transformer wire connections to the input of the UPS (see Figure 15).
Note: You will need a #2 Phillips screwdriver and an Allen wrench.
1. Remove the back panel of the transformer.
2. Tap the line for the proper voltage.
3. Route the wiring from the transformer through the cut-out channel hole provided (see Figure 15).
Figure 15. Tap the Line
4. At the BladeUPS cabinet back panel, install the following for each BladeUPS module (see Figure 16
through Figure 20):