Eaton BladeUPS DoS Installation Instructions P-164000613—Rev 3 21
Section 10 Specifications
This chapter provides the following specifications:
l
Model list
l
Weights and dimensions
l
Electrical input and output
l
Environmental and safety
l
Battery
Table 3. Model List
UPS Model Number
Power Levels
(Rated at Nominal Inputs)
xxx 12 kVA or 12 kW at 208V
See Note
EBM Model Number
BladeUPS EBM
NOTE Derated for line cord and nominal line voltage
Cord Model Number Description Input Plug Type Length
UPSCordPUL 12 kW UL input/output Anderson
See Note
0.5m (1.5 ft)
NOTE Customized Anderson connector for use with Eaton Dual BladeUPS
Table 4. Weights and Dimensions
UPS
Extended Battery Module
(EBM)
Dimensions
(W
DH)
12" x 33" x 46" 438
660 131 mm
17.2”
26.0” 5.2” (3U)
Weights
See Note
Blade UPS model without internal batteries: 60.35kg (133.05lb)
Individual battery: 2 kg (4.4 lb)
Each battery tray: 20 kg (44 lb)
Blade UPS electronics module: 19.5 kg (43 lb)
Blade UPS bypass sel switch: 11.06kg (24.38lb)
77 kg (170 lb)
Table 5. Electrical Input
xxx Model xxx Model
Nominal Voltage 120/208V three-phase 230/400V three-phase
Nominal Frequency 50/60 Hz 50/60 Hz
Frequency Range 45–65 Hz 45–65 Hz
Default Frequency Auto-detected Auto-detected
Rated Input Current 36A 24A
Connections
IEC 309-60A power cord IEC 309-32A power cord
For paralleling, a single Anderson input/output cord connects to the
BladeUPS Bar (see Table 3 on page 21).