22 Eaton BladeUPS DoS Installation Instructions P-164000613—Rev 3
Noise Filtering MOVs and common mode line filter
Input Power Factor
High Efficiency setting: load dependent
Standard setting: >0.99
Input Mode
Three-phase
Table 6. Electrical Output
xxx Model xxx Model
Nominal Output Voltage 120/208 Vac three-phase 230/400 Vac three-phase
Output Voltage Variation
104–132 Vac phase to neutral,
180–229 Vac phase to phase
207–253 Vac phase to neutral,
358–438 Vac phase to phase
Connections
IEC 309-60A power cord IEC 309-32A power cord
For paralleling, a single Anderson input/output cord connects to the
BladeUPS Bar (see Table 3 on page 21).
Short Circuit Capability
(Battery Mode)
84A, <300 ms 44A, <300 ms
Short Circuit Capability
(Normal Mode)
Limited by 50A input breaker Limited by 25A input breaker
Nominal Output Frequency
50–60 Hz auto-detection (Normal mode)
50 or 60 Hz (Battery mode)
Output Frequency Variation
Synchronized (Normal mode)
±0.1 when not synchronized with source (Battery mode)
Output Overload
100–110%: load transfers to Bypass mode after 10 minutes
110–125%: load transfers to Bypass mode after 1 minute
125–150%: load transfers to Bypass mode after 5 seconds
>150%: load transfers to Bypass mode after 300 ms
Voltage Waveform
Standard mode and Battery mode: Sine wave; <2% THD with linear load;
<5% with nonlinear load
Full Output Three-phase
Table 7. Environmental and Safety
xxx Model xxx Model
Surge Suppression ANSI C62.41 Category B3 EN 61000-4-6
Safety Conformance
UL 1778 4
th
edition; CSA C22.2, No. 107.3 UL 1778 4
th
edition, EN and
IEC 62040-1-1
Agency Markings cULus, ICES, CE cULus, CE
EMC (Class A) FCC Part 15 EN 62040-2
Operating Temperature
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 5°C to 25°C (41°F to 77°F)
Storage Temperature 0°C to 25°C (32°F to 77°F)
Transit Temperature -25°C to 55°C (-13°F to 131°F)
Relative Humidity
Operating: 5–95% noncondensing
Non-operating: 5–95% relative humidity, 38.7°C (101.7°F)
Maximum wet bulb temperature with no cosmetic damage
Operating Altitude
Up to 1,000 meters (3,300 ft) above sea level;
up to 2,000 meters (6,600 ft) with 1% derating per +100 meters (330 ft)
Table 5. Electrical Input (Continued)
xxx Model xxx Model