Eaton BladeUPS DoS Installation Instructions P-164000613—Rev 3 23
Transit Altitude Up to 15,000 meters (49,000 ft) above sea level
Heat Dissipation
1432 BTU/hr maximum at 100% rated load (High Efficiency mode)
4094 BTU/hr maximum at 100% rated load (Standard mode)
Audible Noise
Less than 58 dBA at 1 meter typical (Normal mode)
Less than 64 dBA at 1 meter typical (Battery mode)
Leakage Current <3.5 mA
Communication DB-9: 1200–19200 baud
Table 8. Battery
UPS Internal
Batteries
+1 EBM +2 EBMs +3 EBMs +4 EBMs
Configuration (40) 12V, 5 Ah (20) 12V, 9 Ah (40) 12V, 9 Ah (60) 12V, 9 Ah (80) 12V, 9 Ah
Type Sealed, maintenance-free, valve-regulated, lead-acid
Monitoring Advanced monitoring for earlier failure detection and warning
Charging (in minutes) 8–10 times the discharge time
NOTE Charging times are approximate and are to 80% usable capacity at nominal line voltage after full load
discharge.
Table 9. Standalone UPS Battery Runtimes at Full/Half Load (in Minutes)
Model kW
UPS Internal
Batteries
+1 EBM +2 EBMs +3 EBMs +4 EBMs
xxx 12/6 4.7/13.6 9.5/27 17/42 27/60 34/76
xxx 12/6 4.7/13.6 9.5/27 17/42 27/60 34/76
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Table 10. Parallel UPS System Battery Runtimes at Full/Half Load (in Minutes at Capacity)
Number of UPSs kW
UPS Internal
Batteries
+1 EBM +2 EBMs +3 EBMs +4 EBMs
2 24/12 4.7/13.6 9.5/27 17/42 27/60 34/76
3 36/18 4.7/13.6 9.5/27 17/42 27/60 34/76
4 48/24 4.7/13.6 9.5/27 17/42 27/60 34/76
5 60/30 4.7/13.6 9.5/27 17/42 27/60 34/76
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Table 11. Parallel UPS System Battery Runtimes at Full/Half Load (in Minutes with N+1)
Number of UPSs kW
UPS Internal
Batteries
+1 EBM +2 EBMs +3 EBMs +4 EBMs
2 12/6 14/30 27/56 42/89 60/128 76/165
3 24/12 8.7/23 18/42 28/66 43/94 55/120
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
Table 7. Environmental and Safety (Continued)