Eaton BladeUPS 12 kVA Maintenance Bypass Cabinet Installation and Operation Manual P-164000130—Rev 1 www.eaton.com/powerquality 7-1
Chapter 7 Product Specifications
The following tables detail the model characteristics such as input, output, and environmental specifications
for the Eaton BladeUPS Maintenance Bypass Cabinet (MBC). The MBC is a free-standing cabinet with safety
shie
lds behind the doors.
Table 7-1. Model Characteristics
kVA rating 60 kVA
Fault Current
35 kAIC @ 480 Vac
50 kAIC @ 240 Vac
Nominal Current 225A
Size and Weight
W x D x H: 762 mm x 914.4 mm x 2032 mm (30 in x 36 in x 80 in)
Weight: 544.310 kg (1200 lb)
Safety Standards
UL 1778
CSA C22.2 no. 107.1
Table 7-2. Input Ratings
Operating Input Voltage
(Nominal +10/–15%)
480V
Three-phase, three wire plus ground
Operating Input Frequency Range 60 Hz (±5 Hz)
Table 7-3. Output Ratings
Operating Output Voltage
(Nominal +10/–15%)
280V/120V
Three-phase, three wire plus ground
Operating Output Frequency Range 60 Hz (±5 Hz)
Table 7-4. Distribution Characteristics
Panelboards
(2) Cutler-Hammer 42-pole 225A panelboards
NOTE This is
the base Configuration. See A4 in Appendix A, “Installation Reference
Appendices”
for additional configurations.
Bussing Silver-plated
Breakers
225A Cutler-Hammer Series C molded case b
reakers for UOB, RIB, and MBB
125A Cutler-Hammer Series C molded case breakers for SIB
Table 7-5. Transformer Characteristics
Energy Efficiency TP-1 rated
Frequency 60 Hz
K Factor K1
Bussing Silver-plated