Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14 91
20. Wait for the UPS front panel display to illuminate. The indicator flashes on the UPS.
21. Check the UPS front panel display for active alarms or notices (other than “Batteries Disconnected”).
Resolve any active alarms before continuing.
22. Switch the UPS battery circuit breaker to the ON ( | ) position.
23. If optional EBMs are installed, switch all EBM battery circuit breakers to the ON ( | ) position.
24. Verify that the “Batteries Disconnected” alarm has cleared. Verify that no other alarms appear on the UPS
front panel display.
25. Press any button on the front panel display to activate the menu options, and then press the button until
the TURN UPS ON/OFF menu displays.
26. Press the
button to display the TURN UPS ON option; press the button.
27. Confirm the selection. Press and hold the
button for three seconds, until the UPS stops beeping.
a. Verify that the ~ indicator illuminates solid, indicating that the UPS is operating normally and is in
parallel with all other BladeUPS modules in the system.
b. If the indicator is flashing, do not proceed until all alarms are clear. Check the UPS status from the
front panel to view the active alarms. Correct the alarms and restart if necessary.
28. If loads are to be connected to the load connector receptacle, connect the loads before turning on the load
connector breaker.
29. Press the
ESC
button until the Start screen appears.
30. If optional EBMs are installed, see to set the number of installed EBMs.
31. To change any other factory-set defaults.
32. If connecting to a REPO circuit, use procedure on 6.11 Installing REPO for a Parallel System . Use caution
while connecting the REPO as to not EPO operating systems.
44..1188 SSttaannddaalloonnee UUPPSS SSttaarrttuupp
To start up a standalone UPS:
NOTE Verify that the total equipment ratings do not exceed the UPS capacity to prevent an
overload alarm.
1. Plug the equipment to be protected into the UPS, but do not turn on the protected equipment. See
Figure 60 .
2. Make any necessary provisions for cord retention and strain relief.
3. Verify that all UPS circuit breakers are in the OFF (O) position.
NOTE The load connector breaker controls the load connector only, not the output power cord.
4. Verify that the UPS power cord is plugged in.
5. Switch on utility power where the UPS is connected.
6. Remove the breaker ties from the circuit breakers.
7. Switch the UPS input circuit breaker to the ON (|) position.
Standalone UPS Startup