Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14 5
BladeUPS
Modules
BladeUPS Maintenance
Battery Modules
Bottom Entry
Wireways
BladeUPS Bar
Example of a BladeUPS Parallel System
Note the following guidelines when configuring your BladeUPS standalone module or parallel system:
The UPS accommodates a maximum of four EBMs.
The EBMs for a standalone UPS can be mounted directly below the UPS or, with rack side panels
removed, in an adjacent rack to the left or right of the rack containing the UPS.
The EBMs for a parallel system can be mounted in an adjacent rack to the left or right of the rack
containing the UPS (rack side panels removed).
When configured with EBMs, each UPS in a parallel system must have the same number of EBMs
installed.
BladeUPS requires input phase rotation of A-B-C clockwise. Some load equipment may require phase
rotation or phase relationship coordination to ensure proper operation. Review your equipment
manufacturer’s power requirement documents to ensure that your connected equipment operates
correctly.