Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14 43
3. Remove the eight screws on the battery cover plate and retain. Remove the plate and retain (see Figure 26
).
Figure 26. Removing the UPS Battery Cover Plate
4. Slide the battery trays into the cabinet ( see Figure 27 for two battery string installations or Figure 28 for
single-string installations). Verify that each tray is properly aligned before sliding in the tray.
NOTE When installing single-string battery trays for BladeUPS 5.0 kVA, always install the
single-string trays in the bottom battery compartment.
5. When a tray is fully installed, tuck the plastic handle on the end of the tray into place.
Figure 27. Installing the UPS Battery Trays (Two Strings)
Installing the Internal Batteries