User Manual MN04200002E
Effective January 2016
C441 Ethernet module user manual
(C441R, C441T, C441U, C441V)
EATON www.eaton.com
Class 41 (0x29): Control Supervisor Object
Instance Count: 1
Instance List: 1
Table 62. S611 Control Supervisor Instance Attributes
Attrib NV Access
Data
Type Name Description
3 V Set/Get BOOL Run1 Run the softstarter.
7 V Get BOOL Running1 Indicates if the motor is running.
10 V Get BOOL Fault Status A Fault has occurred. Faults are
latching and require a reset.
12 V Set/Get BOOL Fault Reset 0->1 Causes a reset.
13 V Get UINT Fault Code If in faulted state, faultcode indi-
cates the fault that caused the
transition to the faulted state.
15 V Get BOOL Control from
Net
Control is coming from the
network.
101 V Get WORD Device Status Device Bit Array, Bit:
0: Fault
1: Bypass
2: Running1
3: S611 Run/Aux Relay (Relay 1)
4: S611 Fault Relay (Relay 2)
5: CtrlFromNet
6: Permissive
7: Reserved
8: Output #1
9: Output #2
10: Input #1
11: Input #2
12: Input #3
13: Input #4
14: DeviceNet Low Power
15: S611 Intercom Lost
102 V Get UINT Trip Reason Bit = Description
0 = Overload
1 = Jam
2 = Stall
3 = Current Imbalance
4 = Load Disconnect
5 = Phase Loss
6 = Mains Fault
7 = Phase Reversal
8 = Shorted SCR
9 = SCR Not Firing
10 = Pole Overtemp
11 = Bypass Dropout
12 = SCR Overcurrent
13 = Contactor Overcurrent
14 = Communication Fault
15 = Other Device Fault
103 V Get UINT Motor Status Motor Control Status Bits:
Bit = Description
0 = Run
2 = In Bypass
5 = Fault
11 = Relay 1 State
12 = Relay 2 State
13 = Control From Network
14 = Permissive State
105 NV Set/Get UINT Network
Timeout
Network Watchdog or Timeout
enable.
0 = Disable
1 = Enable
106 NV Set/Get UINT Communication
Loss Behavior
1 = Fault
2 = Hold last state
3 = Stop (1)
Table 62. S611 Control Supervisor Instance Attributes (Cont.)
Attrib NV Access
Data
Type Name Description
107 NV Set/Get BOOL Motor Ctrl
Com Loss Act
Disable
When this value is TRUE the
motor state will be unchanged
after a communication loss
event. A FALSE value will
cause the Motor Control
Communication Loss Value to be
applied on a com loss.
108 NV Set/Get BOOL Motor Ctrl Com
Loss Action Val
Action to execute when a com-
munication loss event occurs.
0 = Ignore (No Change)
1 = Stop
109 V Get UINT Fault Code Fault Code and Fault Code List.
When read as a single item it
is the most recent fault. When
read as a list, faults are listed in
history order. Newest are at the
beginning, oldest are at the end
of the list.
If the device is in the Faulted
state, Fault Code indicates the
fault that caused the transition
to Faulted state.
If not in the Faulted state, the
Fault Code indicates the fault
that caused the last transition to
the Faulted state.
110 V Get UINT Fault Code Entry 1
111 V Get UINT Fault Code Entry 2
112 V Get UINT Fault Code Entry 3
113 V Get UINT Fault Code Entry 4 .
114 V Get UINT Fault Code Entry 5
115 V Get UINT Fault Code Entry 6
116 V Get UINT Fault Code Entry 7
117 V Get UINT Fault Code Entry 8
118 V Get UINT Fault Code Entry 9
119 V Set/Get BOOL Clear Fault
Queue
Set this parameter to TRUE to
clear the fault queue.
120 NV Set/Get UINT Fault Enable
Bits
Fault Enable Bits:
Bit = Description
0 = Overload
1 = Jam
2 = Stall
3 = Current Imbalance
4 = Load Disconnect
5 = Phase Loss
6 = Under Voltage
7 = Over Voltage
8 = Voltage Unbalance
9 = Phase Reversal
10 = Ground Fault
11 = Overload On Start
12 = Shorted SCR
13 = SCR Not Firing
14 = Over Temperature
150 V Set/Get UINT Motor Control Motor Control Bits:
Bit = Description
0 = Run
2 = Permissive
3 = Reset
151 NV Set/Get UINT Start Input
Behavior
Selects the behavior for the start
input. When edge is selected,
a start will only be performed
on the rising edge of the start
input. When level is selected,
a start will occur any time the
input is high.
0 = Edge
1 = Level
152 NV Set/Get UINT Fault Relay
Config
Fault Relay Configuration:
0 = Faulted
1 = Not Faulted