Callisto 5PX G2 Service Manual
Checked
:
Rev:
Approved
:
Confidential
This specification is the property of Eaton Corp. and shall not be reproduced or copied or used as the basis for manufacture or sale of apparatus without permission
Fault 107, Site Wiring Fault
Start
Input ground wire is
connected rightly
Connect Ground wireY
Restart UPS and no
alarm?
EndN
Whether the input neutral wire and
live wire are reversely connected
Y
Y
Connect L & N
wire rightly
Y
Restart UPS and no
alarm?
N End
Replace PSDR
Y
Restart UPS and no
alarm?
N
Replace UPS
End
UPS
PSDR
End
Repair detection
circuit
Restart UPS and no
alarm?
N End
CNTL
Replace CNTL
PCBA
Y
Restart UPS and no
alarm?
EndN
Y
Whether the voltage is close to 0
Volt?
Check the voltage between input
neutral wire and ground wire
Check the power
distribution system of the
grid
N
the voltage between input neutral wire and
ground wire
is close to 0 Volt
Restart UPS and no
alarm?
EndN
Y
Repair detection
circuit
Restart UPS and no
alarm?
EndN