Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
48 DualGuard-S US 23
Technical description Field
Dimensions (W x H x D): 1200x600x300 mm
Colour: RAL 7035
Weight: 110 kg
Assembly: Recommended for wall mounting: 4xM8 (min.
2xM8)
Force [N]: 3137
Mounting stability [N]: 1600
Degree of protection: IP54
Protection class: I
Ambient temperature: -5°C to +35°C
Degree of pollution: 2
Electromagnetic compatibility: Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains): UN = 230 V AC A4
Rated current (Mains): IN = 50 A
Rated voltage (Battery): 216 V DC A4
Rated current (Battery): IN =50 A
Rated Frequency: 50 or 60 Hz
Overvoltage category: Mains: III
Max. connected load: At +35°C < 10,8 KW
Maximum numbers of modules:
Controller ACU DG / HMI: 1 A1
PSU: 1 B1
SKU.1 CG-S: B2-D
1x6A 0-23
2x3A 0-23
4x1,5A 0-14
Max. numbers luminaire circuits: 60 A2-4
Terminals:
ACU DG 2,5mm² Rigid/ 1,5mm² flexible A1
Luminaire circuits 4 mm² Rigid/flexible A2-4
Battery feed 35 mm² Rigid/flexible A4
Battery through-wiring 35 mm² Rigid/flexible A4
Mains feed 35 mm² Rigid/flexible A4
Mains through-wiring 35 mm² Rigid/flexible A4