EasyManua.ls Logo

Eaton CEAG DualGuard-S - DualGuard-S ESF30 US SOU2; Technical description

Eaton CEAG DualGuard-S
148 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
134
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
57 DualGuard-S ESF30 US SOU2
57 DualGuard-S ESF30 US SOU2
The DualGuard-S ESF30 US SOU2 sub-station in accordance
with EN 50171 supplies 230V / 216V AC/DC safety and
escape sign luminaires and is particularly suitable for instal-
lation in fire compartments in buildings with a large number
of fire compartments. Thus, the decentralised design of the
system can contribute to reducing the costs for function
maintenance cabling. The automatic test device and indivi-
dual luminaire monitoring with individual status and name
indication per luminaire in conjunction with system-related
ECG / LED supply module including monitoring module
without additional data line reports and proclaims the ope-
rating states.
Consisting of:
Fire protection wall distributor with cable entry from above
and two SOU CG-S 2x4A circuit switches.
Technical description Field
Dimensions (W x H x D): 690x400x230 mm
Colour: RAL 7035
Weight: 51 kg
Assembly: Wand
Degree of protection: IP65
Protection class: II Schutzisoliert nach VDE 0106
Ambient temperature: -5°C to +35°C
Degree of pollution: 2
Electromagnetic compatibility: Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains): UN = 230V AC A1
Rated current (Mains): IN = 9A
Rated voltage (Battery): 216 V DC A1
Rated current (Battery): IN =9 A
Rated Frequency: 50 / 60 Hz
Overvoltage category: Mains: III / Battery: II
Max. connected load: At +35°C < 1,9 KW
Maximum numbers of modules:
SOU CG-S 2x4A 2 A-B
Max. numbers luminaire circuits: 4
Terminals:
Luminaire circuits: 4 mm² Rigid/flexible A-B
Battery feed: 10 mm² Rigid/flexible A1-2
Battery through-wiring: 10 mm² Rigid/flexible A1-2
Mains feed: 10 mm² Rigid/flexible A1-2
Mains through-wiring: 10 mm² Rigid/flexible A1-2
1 2 3 4
A
B
C
D
396
230
685

Table of Contents