Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
40 DualGuard-S LAD 100
Technical description Field
Dimensions (W x H x D): 2070 x 800 x 405 mm
Colour: RAL 7035
Weight: 170 kg
Assembly: Only set up on non-combustible ground (e.g. con-
crete).
Degree of protection: IP21, optional IP31, on request IP54
Protection class: I
Ambient temperature: -5°C to +35°C
Degree of pollution: 2
Electromagnetic compatibility: Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains): UN = 400/230 V AC
Rated current (Mains): IN = 100 A
Rated voltage (Battery): 216 V DC
Rated current (Battery): IN =100 A
Rated Frequency: 50 or 60 Hz
Overvoltage category: Mains: III / Battery: II
Max. Wärmeverlustleistung: At +35°C < 21,6 KW
Maximum numbers of modules:
Controller ACU DG / HMI: 1 E1
PSU: 1-2 E1
BCM.1: 1 E2
SKU.1.1 CG-S: E4
1x6A 0-4
2x3A 0-4
4x1,5A 0-4
Luminaire circuits: 16 D4
Charger CM 1,7A 1-2 E3
Charger CM 3,4A 0-8 F1-4
Terminals:
Luminaire circuits: 4 mm² Rigid / 4 mm² flexible D4
BCM.1: 4 mm² Rigid / 4 mm² flexible D4
ACU DG 2,5mm² Rigid / 1,5mm² flexible D4
Battery feed: 50 mm² Rigid / 50 mm² flexible B4
Battery distribution: 16 mm² Rigid / 16 mm² flexible A4
Mains feed: 50 mm² Rigid / 50 mm² flexible B1
Mains distribution board: 16 mm² Rigid / 16 mm² flexible A1
Order number accesories:
Cupboard base 100mm 40071362282
Cupboard base 200mm 40071362283
Door hinge left 40071362301
Special locking profile half cylinder 40037079790
IP 31 Retrofit kit 40071362296

Table of Contents