97
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
41 DualGuard-S 12C
Technical description Field
Dimensions (W x H x D): 2040 x 800 x 404 mm
Colour: RAL 7035
Weight: 155 kg
Assembly: Ground
Degree of protection: IP21, optional IP31, on request IP54
Protection class: I
Ambient temperature: -5°C to +35°C
Degree of pollution: 2
Electromagnetic compatibility: Industry EN 61000-6-2, Commercial EN 61000-6-3
Rated voltage (Mains): UN = 230 V AC
Rated current (Mains): IN = 60 A
Rated voltage (Battery): 216 V DC
Rated current (Battery): IN =35 A
Rated Frequency: 50 / 60 Hz
Overvoltage category: Mains: III / Battery: II
Max. connected load: At +35°C < 7,56 KW
Maximum numbers of modules:
Controller ACU DG / HMI 1 A2
PSU 1 B2
BCM.1 1 B3
SKU.1.1 CG-S: B4-C
1x6A 0-12
2x3A 0-12
4x1,5A 0-12
Luminaire circuits: 48 A3
Charger CM 1,7A 0-2 B3
Charger CM 3,4A 0-1 C4
Terminals:
Luminaire circuits: 4 mm² Rigid/4 mm² flexible A3-4
BCM.1: 4 mm² Rigid/4 mm² flexible A2
ACU DG 2,5mm² Rigid/ 1,5mm² flexible A2
Battery feed: 16 mm² Rigid/16 mm² flexible A1
Battery distribution: 35 mm² Rigid/35 mm² flexible A4
Mains feed: 16 mm² Rigid/16 mm² flexible A4
Mains distribution board: 35 mm² Rigid/35 mm² flexible A4
Order number accesories:
Cupboard base 100mm 40071362282
Cupboard base 200mm 40071362283
Door hinge left 40071362303
Special locking profile half cylinder 40037079790
IP 31 Retrofit kit 40071362293