15
Technical Data PR202-50-502-22
Effective June 2017
CF2000 System
EATON www.eaton.com
Micro Interfaces
A range of micro interfaces modules are also available:
MIU872 is a compact single zone input, soft addressed, micro-
interface, incorporating integral short circuit isolators. It is fully
compatible with the current range of Cooper analogue fire detec-
tion panels. It is suitable for interfacing a zone of up to 20 conven-
tional Cooper detectors onto a Cooper analogue fire panel. It will
operate with any Cooper conventional detector in configuration
with a schottky diode type base.
MCIM is a compact input module used to accept input signals
from external equipment such as beam detectors, flow switches,
valve monitor switches etc. The CF6000 can be programmed to
perform different actions based on the state of the input. The
maximum number of input devices per loop is 200.