Technical Data PR202-50-502-22
Effective June 2017
CF2000 System
EATON www.eaton.com
Technical Specification (continued)
Outputs
Conventional sounder circuits
Number of sounder circuits 4
Total Sounder Load
1.0A (FH1204)
Maximum Sounder Circuit Load 800mA
Sounder Circuit Fuses (F1/2/3/4) 1.6A (Quick Blow)
End of line resistor 6k8
Fire Routing Equipment
Max Load 60mA
Fused (PTC2) 100mA polyswitch
End of Line resistor 6k8
Fire Protecting Equipment
Max Load 60mA
Fused (PTC4) 100mA polyswitch
End of Line resistor 6k8
Fault Routing equipment
Max Load 30mA
Fused (PTC1) 100mA polyswitch
End of Line resistor 6k8
Auxiliary Relays
The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored.
Max Load 24V 1A
Fuse (PTC5)
1.1A polyswitch
Auxiliary 24V Supply
Nominal Voltage 24V ±10%
Fuse (PTC3) 300 mA polyswitch
Maximum current 30 mA
This output is not to be used for Fire protecting equipment or Fire alarm routing Equipment
Any power taken from the alarm system will affect the standby duration
RS485 Port (Mimic Repeater)
This is a serial output port for driving CF2000 Repeater panels, mimics etc.
This output is short circuit protected
Max Cable Length 2 Km
Min Recommended cable size 1 mm² (Screened)
Mechanical Specification
Weight including batteries
10.6 Kg
Weight excluding batteries 5.3 Kg
Dimensions (Standard batteries) 400 mm (L) x 320 mm (H) x 170 mm (D)
Type of Material (backbox) Mild Steel (Powder Coated)
Type of Material (facia) PC/ABS
Flammability Rating UL 94 V0
Total Number of knockouts 24
Diameter of knockout 20 mm
CAUTION
TERMINAL BLOCKS: DO NOT USE EXCESSIVE FORCE WHEN
TIGHTENING THE SCREWS ON THE TERMINAL BLOCK