25
Technical Data PR202-50-502-22
Effective June 2017
CF2000 System
EATON www.eaton.com
Device input programming
Figure 5. Device Inputs dialog
Device Input Programming
Fire Panel reports fire from device.
Fault Panel reports fault from device.
Reset Panel resets.
Silence Silence all currently active sounders.
Pre-Alarm Panel reports pre-alarm from device.
Non-Latching Device does not latch in alarm condition. Used in conjunction with isolates.
Day/Night Option enables day/night mode on compatible heat and opto-heat detectors.
Optical-Heat Mode switches between heat or optoheat mode.
Heat Mode switches between Heat A1R and Heat CS.
Isolate Zone / Address
User can define between zones or addresses to be isolated on activation of the device.
The isolate list button enables the user to enter up to 8 unique zones or addresses.
If non-latching has been enabled, isolated devices can be un-isolated as the triggered device returns to normal operation.
A call point keyswitch is an example for this application.