EasyManua.ls Logo

Eaton CF2000 - Panel Outputs

Eaton CF2000
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
27
Technical Data PR202-50-502-22
Effective June 2017
CF2000 System
EATON www.eaton.com
Panel Outputs
Figure 7. Panel Outputs dialog
Dependence detection
Each panel output can be assigned a unique list of zones derived
from the zones available on the loop. To activate this output,
two unique zones from this list have to be in fire. Alternatively
any zone outside this list will trigger the output also when the
Dependence
box is checked. The Allocate devices button allows
the user to populate this list.