63
Technical Data PR202-50-502-22
Effective June 2017
CF2000 System
EATON www.eaton.com
Detector Base Wiring CAB300
Supply Voltage 18 - 30V DC
Cable Size 0.5 - 2.5mm²
Recommended cable types FIRETUF, FP200 or MICC
Mounting Hole Centres 50 - 80mm
Wiring Hints
1. Each terminal is suitable for clamping up to 2 wires
2. Clamping of 2 wires of very different diameters under one
screw is not recommended.
3. Suitable for mounting to mounting boxes with 50-80mm fixing
centres.
General
If difficulty is experienced when mounting the sensor, this may be
due to the following:
1. Wiring causing an obstruction - move or shorten wires.
2. Although the base is tolerant to uneven mounting surfaces,
a very uneven surface may cause the base to deform when
the mounting screws are tightened down - loosen screws to
reduce this or slide base to a flat position.
WARNING
DO NOT USE HIGH VOLTAGE TESTERS WHEN SENSORS OR
CONTROL PANEL ARE CONNECTED TO THE SYSTEM
Figure 42. Wiring Diagram for CAB300 Sensor Base