7
Technical Data PR202-50-502-22
Effective June 2017
CF2000 System
EATON www.eaton.com
Compatible Equipment
The range of compatible detectors for the CF2000 system
consists of the following:
Model CAP320 CAH330 CAPT340
Operating voltage 18 to 30V dc
Standby current (max) 220μA
Alarm current (max) 5mA
Ambient Temperature (max)
60ºC
A1R 50ºC
50ºCBS 65ºC
CS 80ºC
Ambient Temperature (min) -20ºC
Alarm temperature (static)
N/A
A1R 60ºC
60ºCBS 77ºC
CS 90ºC
Heat sensor class as defined by
EN54-5:2000
N/A A1R, BS, CS
control panel
selectable
A2S
Relative humidity (no n co nd) 0 to 95%
Height (w/o base) 34mm 43mm
Height (with base) 47mm 56mm
Diameter 100mm
Weight (w/o base) 86g 78g 76g
Material PC/ABS
Colour White
CAP320 Analogue Photoelectric Sensor
This is the most commonly used detector and is most suitable for
detecting slow burning fires.
The status LED can be programmed to either be permanently off
under normal conditions or to pulse in order to confirm that it is in
communication with the CF2000 control panel.
CAPT340 Analogue Photo/thermal Sensor
This is a new addition to the Cooper Fire Systems range of
sensors. It is the ideal sensor for a multi-use environment as it
has an excellent response to smouldering and fast burning fires.
Photo/thermal sensors can be programmed for thermal only opera-
tion at certain times of day.
The status LED can be programmed to either be permanently off
under normal conditions or to pulse in order to confirm that it is in
communication with the CF2000 control panel.