76
Technical Data PR202-50-502-22
Effective June 2017
CF2000 System
EATON www.eaton.com
Micro Zone Monitor Wiring MIU872
To install the device
1. Fit the box in position using the mounting details below.
2. Connect the unit according to the diagram in Figure 55.
3. Recommended Cable Type: FIRETUF, FP200, MICC.
ote:N
No addressing of the interface is required. See control panel
operation for details. There are no serviceable parts so no
maintenance procedures apply.
Figure 55. Standard connections MIU872
1. This unit can only be used with Cooper FXN520 detector base
and compatible.
2. Only connect cable screen to its adjacent earth terminal.
3. The end of line resistor provided must always be fitted, even if
the spur is unused.
4. Maximum spur length - See BS5839 Pt1:2001 for Zone
Coverage.
5. Maximum number of call points allowed is unlimited.
6. Detector zone end of line device is EOLM-1 (supplied).