Micro Input Module Wiring MCIM
To install the device
1. Fit the box in position using the mounting details below.
2. Connect the unit according to the diagram in Figure 56.
3. Recommended Cable Type: FIRETUF, FP200, MICC.
ote:N
No addressing of the interface is required. See control panel
operation for details. There are no serviceable parts so no
maintenance procedures apply.
Figure 56. Standard connections MCIM
1. Only connect cable screen to its adjacent earth terminal.
2. The end of line resistor provided must always be fitted, even if
the input is unused.
3. Monitored inputs can detect open or short circuit faults.