EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Loading and Totals
The general rules are that the panel is capable of supporting up to 200 devices per loop; this can be a
combination of Detection, Callpoints, I/O units, Repeaters and Sounders.
The protocol and internal memory are constructed in such a way that there are certain loading rules
which must be strictly enforced.
Maximum 200 devices per loop
Maximum 60 sounders/beacons/sounder beacons (set low) per loop.
Maximum 20 I/O units per loop which assumes each I/O uses 3 output channels;
Maximum 120 Output channels based on 2 + 3 above.
Certain devices have been constructed to circumvent these rules effectively ‘fooling’ the panel to
offset some of the totals. The maximum 200 per loop CAN NOT be changed.
The totals for EN and UL are the same unless specified in the remarks column.
Optical, Heat or Opto Heat
Sounder/Beacon/Sounder
beacon
Individuals all reply the same
MIO/ULCIO (single and 3 chan)
MIO324S resets on silence
Uses 1 sounder channel,
ULMCOMS resets on silence
MCIM (old version)/ULMCIM
Takes no address – does
take a load.
EN / UL Zone/Shop unit
Monitors (incl. Mini Module)
ZMU/SMU
(Acts as an output device)
Loop loader allows 20
conventional detectors
Repeater/Mimic/CIOP/BS7273
Device
Restricted by load (20) Note
1
Restricted by load (20) Note
1
Addressable Remote Indicator
Table 1
Note 1 – The figure in brackets is a recommended total for these devices, there is currently no
restriction placed in the Loop loader program.
Note 2 – Where total per loop is shown this is a maximum number or a maximum combination with
other output device