16 Amended: April 22
EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
One Man Walk Test.
This function is like the weekly test feature, this allows the engineer to test the complete system
without having to continually return to the panel and reset it. Once all devices have been tested the
‘Stop’ button can then be operated and a manual reset initiated. See also high level menu global
weekly walk tests.
Test Device
This is not a true test of the device. Individual devices can be identified and wiring direction noted
using this menu.
When a device is put into test the fire Led will illuminate a sounder will sound and a relay will switch.
Following an Autolearn test device can be used to indicate cable routes and in what sequence the
panel has numbered the devices etc.
On v3.0 software Next/Previous has been added to enable the user to navigate this function more
easily also the relay of an I/O device will change state.
Auto Learn.
Fig 5
This is the process of addressing the devices on the loop. The process starts by telling every device
to open its Isolator. It then numbers the first device and tells this to close its isolator, the next device is
interrogated and given the next number this continues until all devices are numbered in sequence.
If the Autolearn (all loops) is activated ALL devices on the panel will be numbered in turn, per loop,
sequentially from address 1, in order they appear in the wiring, and be defaulted to a Global Fire
trigger. All zone and device text information will also be defaulted (zone 1 and address no).