23 Amended: April 22
EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
The release dated July 2011 has also introduce extra features within the T1/T2, the first of which
allows the user to select which internal outputs respond to the T1/T2 time delays (see FIG 10)
Fig 10
The second feature allows the user to select which external outputs should respond to the T1/T2 time
delays. This feature is programmed through the device outputs dialog within the Site Installer
program.
All external output devices are defaulted to follow the T1/T2 timer and are unchecked not to follow.
(FIG 11)
[Note: When a loop output device is excluded from T1/T2 within the Site Installer program, it will
ignore the T1/T2 timers completely and follow its Site Installer programming from the point of initial
activation (start of T1 for included devices)]
Fig 11