EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Input Programming General Rules
Fire Event on all panels,
local and network
This is the default
programming
General fault on all panels,
local and network
Performs a Soft reset on all
panels, local and network
Silences local and
networked panels
No indication on display,
creates a log entry affects
local and networked panels
Active from Jul 17
Provides feedback
for FC6 and smoke
management
Sends an Evacuation
command – overrides most
programming on local and
network
Fire/Extinguisher
Activate
No indication on display
creates a log entry Local
Panel Only
Local devices (loop
card) can be
programmed to
respond to this input,
by address (same
loop) or by specified
zone.
No indication on screen –
will initiate a disablement
Led – total number of
addresses to isolate from
this address is 8
Non latch function
not required
No indication on screen –
will initiate a disablement
Led – total number of zones
to isolate from this address
is 8
Non-Latch function
not required
Does not work with
zone grouping
When the fire condition is
removed the panel local and
network performs a soft
reset
When ticked for Day Night
any other device on the
same Loop controller will
follow this signal. When in
night mode a crescent moon
icon appears adjacent to the
top LH corner screen touch
box, no further indication.
Devices affected by
this function are
Opto-Thermal smoke
and Heat detectors.