EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
On release version Jul 12 when all devices are enabled from the 130170 menu the panel will
automatically ‘Hard reset’ to ensure All devices are enabled.
Optical Detector Sensitivity
The sensitivity of the Optical detectors can be reduced by up to 70% to prevent unwanted alarms in
hot dusty environments such as the Far east and India. This feature is outside EN54 specs.
Australian FB Screen
This enables the screen to show Zone or Address text when in Australian mode (see page 20)
Local Zones?
Generally, UK networks use global zones where all 250 allowed zones for the whole network appear
on all panels.
In this case if a shared zone on 2 panels were put into test then the zone would be in test on both
panels.
Some European networks would not be configured in this way, so for these markets ‘Local Zones’
would be selected allowing 250 zones per panel.
Fig 32