46 Amended: April 22
EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
PH2 Software version 3.3.53 (Date ) Improved the functionality of this feature and ensured
compliance with the current EN54
Non-Latching RF Faults.
With the addition of the Addressable and Conventional Radio Fire Hybrid panels and the ability to
network Radio panels, extra features have been added into the menu structure to support these units.
One of which is the ability to select Non-latching faults on the main panel.
Radio devices are highly susceptible to interference and blocked communications from various
sources and as such could go ‘Missing’ for short periods. These periods would generate faults on the
panel so could be classed as nuisance warnings therefore whilst still providing these warnings it
would be unreasonable to expect the user to have to reset the panel every time, so the RF ‘Missing
Address’ faults can now clear when the devices re-establish communications with the panel.
Tamper faults continue to ‘Latch’.
Conventional Sounder Local fires only
This was a special created for specific requirement.
Upload / Download code
This option allows the upload & Download to be PIN protected. When selecting a PIN, DO NOT USE
the same PIN already set for User or Engineer access.
Opto Fire and Fault Threshold override.
The thresholds for fire and fault are defaulted to 60 and 10, these two buttons can be used to lower
these thresholds down to 53 and 3 respectively.
Fig 37