60 Amended: April 22
EMEA Fire Technical Support: DF6000/CF3000 Applications Guide
Fig 54
LED Repeater & Graphical Mimic Relay Board (CIOP4/8)
The 32 way LED and relay mimic boards reply as a repeater when Autolearned, so also need to be
configured correctly within Site installer.
Fig 55
These mimics are configured as a master board and slaves to create up to a total 250 outputs.
The master board takes the loop address and a 24 v DC input, all slaves are connected to this via a
ribbon cable. See Fig 57.
The 250 outputs are configured within Site Installer by applying rules to each output. See Fig 55
The trigger source for the Led or relay can be a fire, fault, disablement or test condition on the panel
or network from either a panel, zone or address. See Fig 56.
The download procedure is now relatively simple;
1. Program the mimic in site installer as per the above diagram applying rules to individual
outputs.