75 Amended: Sept 21
Program Updates
Loop Driver
Loop Driver software can be updated using a Cyclone Pro programming device; alternatively, to
update the software the loop driver will need replacing.
Display
The display program can be updated using a utility program called Panel Prog or via the Site Installer
program. This can only be carried out in this manner on the latest display software release;
Display 3.02.03, Loop: 3.2.01 Dated 15 Aug 08. This is also available on the Single and 2 loop
DF6100 and 61002, and CF1100/1200 panels.
Any update for the CF2000 can only be achieved on panels Dated later than Jan 2015 (software
version 1.26.06) or later.
Alternatively, to update earlier versions of software the display micro will need replacing.
NOTE In all instances a download of the program will be required prior to any upgrade
The display program can be updated using the Panel Prog program and Hyperlink as follows;
1. Connect Laptop to the panel via the serial port.
2. Open HyperTerminal program and apply a name in the new connection box. Click OK
3. Select Com 1 in the ‘connect to’ box. Click OK
4. In the Comm 1 properties box set - 38400 baud, data bits 8, parity none, stop bits 1 and no
flow control.
5. Data will now start scrolling down the screen area.
Fig 67
6. In HyperTerminal, press ctrl-x, and then 'y' immediately. This will erase the current program in
the display micro.
7. Wait until the text "WAITING FOR PROGRAM" appears in HyperTerminal window.
8. Close HyperTerminal.

Table of Contents