62 CF3000 INSTALLATION AND OPERATION MANUAL 25-14682-A July 2019 www.eaton.com
PC commissioning software
PC commissioning software
Device Inputs
Device input programming
Fire = panel reports fire from device.
Fault = panel reports fault from device.
Reset = panel resets.
Silence = silence all currently active sounders.
Technical/Input = No indication on display, creates a log entry.
Evacuate = Sends an evacuation command.
Fire/Extinguisher Activate = German mode only.
FRE Activate = German mode only.
None Fire = No indication on display, creates a log entry.
Cascade = Selects a delay in seconds on the device within the list This will go to
alarm after the selected time so can be used as a further trigger source.
Isolate Addresses = This allows a group of addresses (max 8 on the same loop) to
be isolated from the trigger. Panel does not go to Fire, trigger is non-latching
Isolate Zones = This allows a group of zones (max 8) to be isolated from the
trigger. Panel does not go to Fire, trigger is non-latching