EasyManua.ls Logo

Eaton Cooper Power Form 6-TS - Page 35

Eaton Cooper Power Form 6-TS
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Form 6 triple-single microprocessor-based rack mount recloser control
31INSTALLATION AND OPERATION INSTRUCTIONS MN280084EN July 2018
TX
RX
NON-ECHO
Serial Fiber
Ethernet 100 Base-FX
Type 2
Ethernet 10/100 Base-T,
100 Base-FX
Type 3
Ethernet 10/100 Base-T
Type 1
#2 #1
Standard
(No Communication Option)
IRIG-B
J5
RS-485 Communication
RS-485 C
-
+
RX
TX
#2
#1
#2 #1
IRIG-B
J5
J4 – ETHERNET – J3
2 1
IRIG-B
J5
J4 – ETHERNET – J3
2 1
IRIG-B
J5
J4 – ETHERNET – J3
2 1
IRIG-B
J5
IRIG-B
J5
Ethernet 100 Base-FX
Type 4
Default
Primary
Ethernet
Interface
#2 #1
IRIG-B
J5
J4 – ETHERNET – J3
2 1
Figure23. Back panel ethernet and communication options
The Ethernet communication card accessory is offered in
3physical layer configurations (twisted pair and optical-fiber
options) as shown in Table9.
Table9. Ethernet communication card configurations
Type Card
configurations
Output
connectors
Communication
speed
1 10/100 Base-T 2 * RJ-45 10 / 100MBps
(auto switching)
2 100 Base-FX
(multi-mode fiber)
2 * MT-RJ 100MBps
(full duplex)
3 10/100 Base-T,
100 Base-FX
RJ-45 + MT-RJ 10/100MBps
and 100MBps
4 100 Base-FX,
(single-mode fiber)
2 * LC 100MBps
(full duplex)
Maximum link length is determined by the use of the
particular physical layer implementation, and can be further
constrained by the actual network configuration. In case of
the 100Base-FX MT-RJ connector based implementation,
maximum link length in excess of 2000m can be achieved
with 62.5/125µm multi mode fiber. The fiber-optic link uses
1300nm wavelength, and can easily be interfaced to other
100Base-FX solutions (ST connector patch cord solution).
The Ethernet communication accessory card (Figure23)
is equipped with two physical ports configured to act as
primary and standby LAN connections. Availability of the
backup communication port enables creation of highly
redundant Ethernet networks thus increasing the overall
system reliability.
ote:N Under normal network conditions, all
communications will be channeled through the
primary port (#1, Figure23), with the standby
port either logically disabled, or configured for fast
automatic throw-over in case of the primary Ethernet
link failure. Refer to Service Information S280-70-9
(ProView 4.X.X) or S280-70-23 (ProView 5.X.X) Form
6-TS Control Programming Guide for additional
Ethernet accessory configuration information.

Related product manuals