EasyManua.ls Logo

Eaton Crouse-hinds series - External Pushbutton Terminals

Eaton Crouse-hinds series
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
TM293 MEDC DB3BM UL Technical Manual
SOUNDER/HORN – DB3BM UL TM293.A August 2022 www.eaton.com
6.0 CERTIFICATION / APPROVALS
UL listed for use in USA (USL) and Canada (CNL)
Please refer to the marking on the unit for specific
approval details
(USL) Zone 1, AEx db IIC Gb T*
Zone 21, AEx tb IIIC Db T*
Class I, Division 1, Groups A, B, C & D
(CNL) Ex db IIC Gb T*
Ex tb IIIC Db T*
Class I, Division 1, Groups B, C & D
Also suitable for: Class I, Division 2, Groups A, B, C & D
Class II
Division 2 Groups F&G
Class III Division 2
Applicable Standards:
(USL) UL60079-0, Edition 7
UL60079-1, Edition 7
UL60079-31, Edition 2
UL1203, Edition 5
(CNL) CSA C22.2 No. 60079-0 :Edition 4
CSA C22.2 No. 60079-1:16
CSA C22.2 No. 60079-31:15
CSA C22.2 No. 30-M1986,
Edition 3 R2016
*T-Ratings:
Max. Power
rating
T
amb.
T
G
T
D
15W -60°C to +85°C T4 T135°C
-60°C to +55°C T5 T100°C
-60°C to +40°C T6 T85°C
Electrical Ratings
1. 12 V to 48 Vdc, 716 mA to 171 mA, Special Application†
2. 24V Vdc regulated 356mA
3. 110 Vac, 50/60 Hz, 122mA, Special Applicaton.
4. 120 Vac, 50/60 Hz, 110mA, Regulated.
5. 220/230/ Vac, 50/60 Hz, 63 mA, Special Application.
6. 240 Vac, 50/60 Hz, 58 mA, Regulated
ote: N the DC special application version is suitable for
use with 24Vdc regulated supplies.

Other manuals for Eaton Crouse-hinds series

Related product manuals